5.0 COMMUNICATION PROTOCOLS
The Din-Mon™ meter supports multiple communication protocols. Refer to section 2.1
Ordering Information to check your meter model configuration to determine which
protocol(s) it supports.
Refer to section “Wiring the Communications” for wiring details.
Refer to section “Setting Communication Protocol” for selecting available protocols.
If the protocol you need is not listed in the menu selection, verify the model number
you ordered.
Refer to the Appendices for Modbus point maps, BACnet objects, and LonWorks
SNVTs.
5.1.1 Modbus RTU
The Din-Mon™ Modbus RTU meter communicates with building automation
equipment over a 3-wire (3-conductor) RS-485 network using Modbus RTU protocol.
The meter is shipped with a Modbus ID number of 1. The Modbus ID range is 1 to 247.
There can be no duplicate numbers on a RS-485 network, so caution must be taken
when assigning a meter ID number prior to its installation on the network.
5.1.2 BACnet MS/TP
The Din-Mon™ BACnet MS/TP meter communicates with building automation
equipment over RS-485 network using BACnet MS/TP protocol.
The meter is shipped with a BACnet instance device ID number of 1 and MS/TP MAC
of 1; both of these numbers must be unique within an MS/TP network.
The meter MS/TP MAC can be numbered from 0 to 127; the MAX Master range is 1 to
127; the BACnet instance device ID range is 0 to 4194303.
5.1.3 Baud Rate and Settings on RS-485
RS-485 communication can operate at different baud rates (speed). The baud rate is
selected via the LCD display menu. There are 4 baud rate selections: 9600 (factory
default), 19200, 38400, and 76800 baud; higher baud rates would require shorter
cable length. The setting is 8-parity bits, no-parity, 1-stop bit.