Owner's manual

DIN-MON™ SMART METER
21 62-0442—04
4.5.1 Installing Split-Core Current Sensor Assembly
1. Each phase being monitored will require one split-core current sensor assembly.
Open the current sensor assembly by lifting the top off the sensor.
Fig. 14. Typical Split Core Current Sensor.
2. Reassemble the current sensor assembly around the conductor(s) to be moni-
tored. Ensure the current sensor side marked “This Side Toward Source” is fac-
ing the source side of the metered conductor.
3. Run the Black and White wires from the current sensors to the meter and install
them according to the standard installation diagram.
Fig. 15. Split Current Sensor Dimensions.
P/N AMPSABCDE NOTE
50082281-006 100 2.00 2.10 0.60 0.75 0.75
50082281-008 200 3.25 3.35 1.00 1.25 1.25
50082281-010 400 3.25 3.35 1.00 1.25 1.25
50082281-012 800 4.75 5.00 1.20 2.00 2.00
M35137
SOURCE
LOAD
M35102
E
B
A
D
C