Owner's manual

DIN-MON™ SMART METER
11 62-0442—04
Battery Cell Description Non-rechargeable Cell Used
For Memory Retention and
RTC
Manufacturer Panasonic
Manufacturer Part No CR2032
Working Voltage 3 VDC
Current Capacity 225 mAHr
Electrolyte Manganese Dioxide Lithium
RS-485 Serial
Communications
Cable UL-listed stranded conductors
22-26 AWG, Belden 3106A (3-
wire)
Input / Output Voltage Grounded-isolated +/-5.4 VDC
Cable Connector Screw terminal termination
Circuit Input Isolation 5.3 kVAC
Max Cable Distance 4,000 feet
Max Network Nodes 64 cabling nodes
Max Baud Rate Up to 76.8 kpbs
Ethernet
Communications
Cable UL-Listed CAT-5e cable,
8-conductor, stranded 24 AWG
Cable Connector RJ-45
Protocol 10/100-Base-T
Cable Distance 450 feet
LonWorks
Communications
Cable Stranded Twisted 24 Awg.
TIA 568A Category 5
Cable Connector Screw Terminal Terminations
Protocol TP/FT-10
Twisted Pair/Free Topology
Max Cable Distance Single Terminated:
820 feet (device to device)
1476 feet (total wire length)
Doubly Terminated:
3280 feet (max bus length)
10 feet (max stub length)
Max Network Nodes 64 Devices/Nodes on single
network
Max Baud Rate 78 kbps bit rate
Outputs 1 and 2 Contact Closure N.O. Dry
Contact Rating (max.) 100mA, 60V AC or VDC
Mating Connector Screw terminal plug (2-wire)