Datasheet
234
v1.6 / Modification rights reserved
EE820
Support Literature
www.epluse.com/ee820
Ordering Guide
Order Example
EE820-H1A3E9
EE820-HV2J3E1AM4P1BD6
CO
2
range: 0...2 000 ppm
Output: 0-10 V
Electrical connection: M12 plug
Response time: standard
CO
2
range: 0...5 000 ppm
Output: RS485
Electrical connection: M16 cable gland
Respnse time: fast
Protocol: Modbus RTU
Baud rate: 19 200
Accessories (see data sheet „Accessories“)
USB configuration adapter HA011066
Product configuration software EE-PCS
(free download: www.epluse.com/EE820)
Mating M12x1 connector for self assembly HA010707
Connection cable M12x1 socket - flying leads
- 1.5 m (3.3ft) HA010819
- 5 m (16.4 ft) HA010820
- 10 m
(32.8 ft) HA010821
Protective cap for female M12 connectors HA010781
Protective cap for male M12 connectors HA010782
Power supply adapter V03
EE820-
Hardware configuration
CO
2
range
0...2 000 ppm HV1
0...5 000 ppm HV2
0...10 000 ppm HV3
Output
0-5 V A2
0-10 V A3
4-20 mA A6
RS485 J3
Electrical connection
M16 cable gland E1 E1
M12 plug E9
Response time
standard no code
fast (with forced air circulation) AM4
Setup RS485
Protocol
Modbus RTU
1)
P1
BACnet MS/TP
2)
P3
Baud rate
9 600 BD5
19 200 BD6
38 400 BD7
57 600
3)
BD8
76 800
3)
BD9
1) Factory setting: Even Parity, Stopbits 1; Modbus Map and communication setting: See User Guide and Modbus Application Note at www.epluse.com/ee820.
2) Factory setting: No Parity, Stopbits 1; Product Implementation Conformance Statement (PICS) available at www.epluse.com/ee820.
3) Only for BACnet MS/TP.