Datasheet

37
EE071
v1.8 / Modification rights reserved
EE071-HTPBAE1
Model: humidity & temperature
Housing: polycarbonat
Filter: membrane filter
Configuration: baud rate 9600, even parity, 1 stopbit
- M12x1 flange coupling with 50mm
(2“) litz wire (HA010705)
- filter caps (HA0101xx)
Connection Diagram
Ordering Guide
Order Example
Accessories
M12x1 flange coupling with 50mm (2“) litz wire (HA010705):
brown...+UB
white.....B-RS485
blue......A-RS485
black....GND
grey......shielding
M16x1.5
1...+UB
2...B-RS485
3...A-RS485
4...GND
EE071:
Modbus Map
Register
addresse
Protocol
addresse
Parameter
name
30026 19 Temperature [°C]
30028 1B Temperature [°F]
30030 1D Rel Humidity [%]
30032 1F Abs Humidity [g/m³]
30034 21 Dew Point [°C]
30036 23 Dew Point [°F]
30038 25 Mixing ratio [g/kg]
Register
addresse
Protocol
addresse
Parameter
name
30040 27 Temperature [°C]
30041 28 Temperature [°F]
30042 29 Rel Humidity [%]
30043 2A Abs Humidity [g/m³]
30044 2B Dew Point [°C]
30045 2C Dew Point [°F]
30046 2D Mixing ratio [g/kg]
Register
addresse
Protocol
addresse
Parameter
name
40001 00 Slave-ID
The measured values are saved as a 32Bit float value from 0x19 to 0x25 and as 16Bit signed integer between
0x27 and 0x2D. The factory setting for the Slave-ID is 247 as an integer 16Bit value.
This ID can be customised in the register 0x00 (value margin 1 - 247 permitted).
The serial number is located as a128Bit value from 0x1D.
FLOAT:
INTEGER:*
INTEGER:
* Values are stored with a scaling of 1:100
(e.g.: 2550 is equivalent to 25.5°C)
MODEL HOUSING FILTER BAUD RATE PARITY STOPBITS
Humidity and Temperature (HT) polycarbonat (P) membrane lter (B) 9600 (A) odd (O) 1 stopbit (1)
metal (M) metal grid lter (polycarbonat) (C) 19200 (B) even (E) 2 stopbits (2)
PTFE - lter (E) 38400 (C) no parity (N)
metal grid filter (stainless steel)
1)
(I)
EE071-
1) The metal grid filter (stainless steel) is only available in combination with metal housing (M).