Product specifications
Page 142 of 146 198-1600-00 Rev F
68
Inverter
Control
(0 to n)
Invalid inverter communications
response to the process controller
request for module A calibration
data.
The process controller continues
to request the module
calibration data until it receives
a valid response, then the fault
clears.
YES
YES
69
Inverter
Control
(0 to n)
Invalid inverter communications
response to the process controller
request for module B calibration
data.
The process controller continues
to request the module
calibration data until it receives
a valid response, then the fault
clears.
YES
YES
70
Inverter
Control
(0 to n)
Invalid inverter communications
response to the process
controller’s request for a change
in module A output waveform
settings.
The process controller continues
to request the change in output
waveform until it receives a valid
response, then the fault clears.
YES
YES
71
Inverter
Control
(0 to n)
Invalid inverter communications
response to the process
controller’s request for a change
in module B output waveform
settings.
The process controller continues
to request the change in output
waveform until it receives a valid
response, then the fault clears.
YES
YES
72
Inverter
Control
(0 to n)
Invalid inverter communications
response to the process
controller’s request for module A
output waveform settings.
The process controller continues
to request the output waveform
settings until it receives a valid
response, then the fault clears.
YES
YES
73
Inverter
Control
(0 to n)
Invalid inverter communications
response to the process
controller’s request for module B
output waveform settings.
The process controller continues
to request the output waveform
settings until it receives a valid
response, then the fault clears.
YES
YES
74
Inverter
Control
(0 to n)
Invalid inverter communications
response to the process
controller’s request for module A
waveform average readings.
The process controller continues
to request the output waveform
average readings until it
receives a valid response, then
the fault clears.
YES
YES
75
Inverter
Control
(0 to n)
Invalid inverter communications
response to the process
controller’s request for module B
waveform average readings.
The process controller continues
to request the output waveform
average readings until it
receives a valid response, then
the fault clears.
YES
YES
76
Inverter
Control
(0 to n)
Invalid inverter communications
response to the process
controller’s request for combined
output module waveform average
readings.
The process controller continues
to request the output waveform
average readings until it
receives a valid response, then
the fault clears.
YES
YES
77
N/A
N/A
N/A
N/A
N/A
78
Inverter
Control
(0 to n)
The process control received a
NAK response from the inverter
control multiple times
Used for trouble shooting only,
not enabled in production
controls
NA
NA
79
Inverter
Control
(0 to n)
The process control did not
receive a response from the
inverter control to one or more
requests.
The process controller continue
to make requests until all
requests receive valid
responses, then the fault clears.
YES
YES
80
System
(0)
The model type in the process
controller EEPROM has not been
set (Model Type = 0xFF)
The power supply configuration
needs to be updated.
YES
NO
81
System
(0)
Calibration data could not be
saved
Calibration did not complete.
Calibrate again. If the fault
persisits contact Dynatronix, Inc.
NO
YES