Product specifications
Diamond 10kW Manual Dynatronix, Inc.
198-1603-03 Rev 01 Page 135 of 150
B.1.19 Unit Settings Command “t”:
@AA.a
Sync character (@) and unit address, AA = Unit ID (0 to 99; 0 is a
global ID), a (n/a, set to zero)
t0
Command character and Type – 0=read, 1=set, 2=activate(n/a),
3=ack, 4=nak
#16,
Number of fields character and number of fields after the comma,
excluding CRC
0,
Control Type 0=Panel, 1=Host, 2=Analog/Panel, 3=Analog/Host
ctl
1,
unit address – 1 to 99, (unit address used in the header of each
command)
addr
0,
Host port baud rate – 0 = 9600 (default), 1 = 19200, 2 = 38400, 3 =
57600, 4 = 115200
bps
0,
Power Up Mode – 0 = always start in standby, 1 = return to last state
pwr
0,
Power Fail Error Enable - 1 = enable power failure errors, 0 = disable
power failure errors (when disabled the error codes are still logged to
the error history log, but they are not displayed on the front panel or
reported to the host in the “m” alarm status message). There is a
separate error code for a brief power failure (error code 103) that did
not cause a complete power loss but did disable the output, and a
complete power loss (error code 102).
pf
0,
Front panel operate switch enable (0 = locked, 1 = enabled) (pots and
meters display only)
opsw
0,
Front panel remote switch enable (0 = locked, 1 = enabled) (pots and
meters display only)
rmsw
0,
Clear Active Errors ( 0 = no action, A numeric value clears the
associated error code, 32767 clears all active error codes). If the
error conditions still exists after an error code is cleared the error code
will be set again. The action of setting this parameter to a non-zero
number clears the associated alarm, the value of this parameter is not
stored and will always be read as zero.
eclr
0,
Digital Input Configuration: 0 = Disabled, 1 = Operate On Close, 2 = 1
Push For Operate, 3 = 2 Push for Operate, 4 = Operate On Close and
inhibit on open (operate not allowed if contact is open, see "on 3" in
the user manual). For complete descriptions of each Digital input
configuration see the user manual.
dst
0,
Front Panel Run Screen Select: 0 = meters, 1 = totalizer status, 2 =
cycle status, 3 = expectd average current in current regulation mode
CH1, 4 = expectd average voltage in voltage regulation mode CH1, 5
= expectd average current in current regulation mode CH2, 6 =
expectd average voltage in voltage regulation mode CH2 (screens 3
to 6 are diagnostic screens) (only used for the pots and meters
display)
scr
0,
Front Panel Error Message Disable – 1 = Disable display of error
codes on the front panel, 0 = enable display of error codes on the
edis