Product specifications
Page 114 of 150 198-1603-03 Rev 01
21. Slaves will not send a response to messages directed to the global address (device
address 00). All slaves on the network will perform the requested action if they properly
receive the command, however no response is sent.
B.1.5 Unit Addressing (@AA.a)
Unit ID ‘AA’
Channel
ID ‘a’
Description
00
0
Directed to all channels on all units
01
0
Directed to all channels on unit 1
99
0
Directed to all channels on unit 99
02
1
Directed to channel 1 on unit 2
For single channel supplies set the channel ID to one.
No response is sent to commands directed to the global unit ID (00).
B.1.6 Communications Settings (factory default) – RS485
Baud Rate
Bits
Parity
Stop Bits
Handshake
*115200
8
none
1
none (master-slave)
The RS485 host port can be operated on a multi-drop bus (multiple power supplies
connected to a single host, all using the same communications cable). The host (master) is
always listening unless sending a command. Slave units are always listening for
commands unless sending a response. Slave units only respond to commands that
contain their address.
* The baud rate is selectable, see B.1.19:Unit Settings Command “t”: to set the baud rate
using the host port. See 6.3.2:Host Port Configuration to set the baud rate using the
control panel.