Operating instructions
Swim Spa Operator’s Guide
CAUTION - RISK OF ELECTRIC SHOCK.   Do not leave the CD 
compartment open.
12)
WARNING - TO REDUCE THE RISK OF INJURY (CONT): 
IMPORTANT SAFETY INSTRUCTIONS
READ AND FOLLOW ALL INSTRUCTIONS
CAUTION - RISK OF ELECTRIC SHOCK.  Replace components only 
with identical components.
NOTE - The CD player controls are not to be operated while inside the swim spa.
WARNING - PREVENT ELECTROCUTION. Do not connect any 
auxiliary components (for example, additional speaker, headphones, additional audio/video 
components etc.) to the system. These units are not provided with an outdoor antenna.
Do not service this product yourself as opening or removing covers may expose you to 
dangerous voltage or other hazards. Refer all servicing to your qualied swim spa tech.
If the power supply/supply cord(s) are damaged, if water is entering the speaker, CD 
compartment, or any other component in the electrical equipment compartment area, the 
protective shield is showing signs of deterioration, or there are signs of other potentially 
hazardous damage to the unit, turn off the circuit breaker from the wall and contact or refer to 
your service technician.
The unit should be subject to periodic routine maintenance once every quarter to make sure 
that the unit is operating properly.
DANGER - RISK OF ELECTRIC SHOCK. Do not permit any electric 
appliance, such as a light, telephone, radio or television within ve (5) feet of the swim spa. 
A green colored terminal or a terminal marked G, GR. Ground, Grounding or the symbol shown 
in Figure 14.1 of UL1563 is located inside the supply terminal box or compartment. To reduce 
the risk of electric shock, this terminal must be connected to the grounding means provided in 
the electric supply service panel with a continuous copper wire equivalent in size to the circuit 
conductors supplying this equipment.
Do at least two lugs marked “Bonding Lugs” are provided on the external surface or on the 
inside of the supply terminal box or compartment. To reduce the risk of electric shock, connect 
the local common bonding grid in the area of the swim spa to these terminals with an insulated 
or bare copper conductor not smaller than No. 6 AWG.
All eld-installed metal components such as rails, ladders, drains or other similar hardware with 
3m of the swim spa shall be bonded to the equipment grounding bus with copper conductors 
not smaller then No. 6 AWG.
13)
14)
15)
16)
17)
18)
•
•
•