User Manual

06-DPP-UM-00147 02/12 33
INTERNAL POWER CONFIGURATION
Ensure that jumpers are in place at JP1 and JP2 on the module – reference Figure 3.10B. In this congu-
ration, the 4-20 mA output is driven from a +24 VDC source located within the DFX ow meter. The 24
VDC source is isolated from DC ground and earth ground connections within the DFX instrument. The
module can accommodate loop loads up to 800 Ohms in this conguration.
NOTE: The +24 internal supply, if congured to power the 4-20 mA output, shares a common ground with another ISO-MOD (if
installed). If another module is connected to earth ground, a ground loop may occur. The solution to this problem is to congure
the 4-20 mA module for external power and utilize an external isolated supply to power the 4-20 mA loop.
EXTERNAL POWER CONFIGURATION
Remove the two jumpers located at JP1 and JP2 on the module – reference Figure 3.10C. In this con-
guration the 4-20 mA module requires power from an external DC power supply. The voltage of the
external power source must be sucient to power the module and drive the loop load. The loop loss
attributed to the ISO-MOD is 7 VDC, so the minimum voltage required to power a loop can be calculated
using the following formula:
Loop voltage (min) = (loop load Ohms × 0.02) + 7
OUT (-)
IN (
+
)
I/O: 4-20 mA
P.N. D020-1045-100
ISO-MOD
JP2
JP1
INT PWR EXT PWR
Use Both
Jumpers
RTU/PLC
MONITOR
4-20 mA IN (+)
4-20 mA OUT (-)
FIGURE 3.10B  INTERNALLY POWERED 420 mA