Technical data
A
A.20
GE Power Controls
Circuit Protection
Applications
Approval / Marking
Add-on devices
G60
Performances
IEC 60898
IEC 60947-2
6000
3
10kA
Miniature Circuit Breakers
Auxiliaries
Motor
operator
Add-on RCD
Thermal setting In (A) 2-63
Rated voltage AC Un (V) 240/415
Minimum operating voltage U
B min (V) 12
Tripping characteristics B-C-D
Selectivity class 3
Mechanical/electrical endurance 20000/10000
Tropicalisation acc.to IEC 60068-2 95%RH at 55°C
Terminal capacity flexible/rigid cable(mm
2
) 25-35
Poles 1, 1+N, 2, 3, 4
Weight (g/pole) 120
Short-circuit capacity
AC acc. to IEC 60898
Poles V Icn/Ics (kA)
1-4 230/400 6
AC acc. to IEC 60947-2
Poles V Icu (kA)*
1 240 10
1+N, 2 127 30
240 20
2 415 10
3, 4 240 20
415 10
*Ics = 75% Icu
DC acc. to IEC 60947-2
Poles V Icu/Ics (kA)
16020
2 125 25
Accessories
Busbars
More technical data
Dimensions
pg A.35
pg E.1
chap. T1
pg A.36
Add-on RCD
Auxiliary contacts
Shunt trip
Undervoltage release
Panel board switch
Motor operator
pg B.14
pg C.4
pg C.6
pg C.6
pg C.6
pg C.8