Technical data
technical data
A single bi-coloured alarm
LED is provided on the call
point. This LED is controlled,
independently of the call
point, by the control panel.
The red LED is lit when the call
point has been activated. An
amber/yellow LED indicates
a fault.
Call points can be remotely
tested from the panel by
transmission of a single
bit in the communications
protocol. Call points respond
by providing a value of 64
which corresponds to the
alarm value.
XP95 Manual Call Points are
available with or without
XP95 MANUAL CALL POINT
XP95 Manual Call Point (MCP)
OPERATING
PRINCIPLES
The new Apollo XP95
EN54-11:2001 compliant
Manual Call Point (MCP) is
based on the KAC conventional
MCP range. It is electronically
and mechanically backward
compatible with previous
Apollo call points based on
KAC’s World Series product.
The address of each
call point is set at the
commissioning stage by
means of a seven-segment
DIL switch.
Fig.16 Typical response characteristic - XP95 Manual Call Point
an isolator. Each version is
available with a resettable
element and a backbox for
surface mounting as standard.
If a glass is required, it is
available on request. For all
part numbers please refer to
Table 2.
To provide additional
protection against accidental
operation, a transparent
hinged cover with a locking
tag, part number 26729-152 is
available, which can be fitted
to the manual call point.
Please note that the call
point does not conform to
EN54-11:2001 when this lid
is fitted and secured with the
locking tag. For
weatherproof call points see
Discovery guide PP2052.
Important Note – the use
of lubricants, cleaning
solvents or petroleum
based products should
be avoided.
Colour Deformable Backbox Pattress Isolated Non-
Element for surface Box isolated
Wiring
55100-905 Red
• •
•
55100-908 Red
•
•
•
Table 2
page
15