Installation manual

DMC810GL Installation Manual Rev E.docx 2
features
Single Phase Supply
Simple supply requirement, single phase at 40A.
4 Dimmed Outputs
Each dimmed 10A output is independently
regulated, protecting loads from voltage surges
and spikes. These outputs are overload protected
by a single 10A circuit breaker shared with a
switched output.
4 Switched Outputs
Each switched output is rated at 10A. These
outputs are overload protected by a single 10A
circuit breaker shared with a dimmed output.
4 Control Outputs
Each of the 4 optically isolated outputs can be
configured to be either DALI Broadcast, 1-10V, or
DSI control, covering the latest types of HF
Fluorescent Ballasts and dimmable electronic
transformers. These outputs can operate in
tandem or independently of the switched outputs.
Convection Cooled
This device is naturally aspirated, requiring no
mechanical cooling system when installed in
accordance with these instructions.
Many Control Options
Control of this device can be from a combination
of available methods, eg. serial control port, relay
contacts, push button wall stations, infra red
receivers and timeclocks. Easy high level
interface to other popular AV control systems and
Building Management Systems (BMS) is also
available.
Simple Installation
Wall mount enclosure with mounting lugs
facilitate installation. Cable knockouts are
provided, at the top & side of the enclosure for
supply and load cables, with safety extra low
voltage (SELV) control section at the bottom.
important safeguards
Warning This is a class A product. In a domestic
environment this product may cause radio
interference, in which case the user may be required
to take adequate measures.
Instructions We recommend that you read this
Manual prior to installation, retain it and give the end
user.
Troubleshooting - If problems are encountered,
check the “Troubleshooting” section on page 8.
Special Programming Once powered and
terminated correctly this device will only operate in
basic mode. A new Dynalite panel will turn on all
lighting channels from button 1 and turn off from
button 4 if network terminations are correct. Only once
the full network is test correct can commissioning
begin. Advanced functions can be commissioned via
Envision software. If commissioning is required,
contact your local distributor for details.
Check Connections Treat this device as a
switchboard that has been shipped. Tighten all load-
carrying screw connections, as vibrations from
transport can cause MCB and terminal block screws to
become loose.
Power Sources This device should only be
operated from the type of supply specified on the front
panel. This device must be earthed.
Dimmed and Switched Output Circuits The load
on a circuit should not exceed the specified capacity of
10A for a dimmed channel and 10A for a switched
channel. Loads should be calculated to ensure that
the overall maximum capacity of 40A (10A per pair of
dimmed & switched channels) is not exceeded.
Ballast Control Load Control Circuits If this
device is being used to control DALI, 1-10V or DSI HF
Fluorescent Ballasts, a 2 core LV insulated control
cable is required to be run to the loads, in addition to
the mains feed. Note that the ballast control outputs
are not SELV as they are not double insulated from
mains.
Load Type Default is for ballast load control outputs
to be 1-10V. Check to see what type of HF
Fluorescent Ballasts are in the luminaries. When
connecting 1-10V load control lines, pay attention that
the correct polarity is maintained.
Mounting Location Device must be mounted right
way up, on a vertical surface (refer to page 4 for
mounting instructions). The specified minimum
clearance of 100mm for all sides must be adhered to.
Install in a dry, well-ventilated location. Controllers
may emit some mechanical noise. Take this into
account when deciding the mounting location.
Data Cable The recommended cable for
connections to the serial port is screened, stranded
RS485 data cable with three twisted pairs. Part
numbers for various manufacturers are listed on page
6. This cable should be segregated from mains cables
by a minimum distance of 300mm subject to local
wiring regulations. If anticipated cable runs are over
600 metres for serial cables, consult your dealer for
advice. Do not cut or terminate live data cables.
Warning
TO REDUCE THE RISK OF FIRE OR
ELECTRIC SHOCK, DO NOT EXPOSE
THIS DEVICE TO RAIN OR MOISTURE.
DO NOT ENERGISE UNLESS THE
FRONT COVER IS IN PLACE.
THIS DEVICE MUST BE EARTHED.
INSTALLATION, PROGRAMMING AND
MAINTENANCE MUST BE CARRIED OUT
BY QUALIFIED PERSONNEL