SWTD-1000 Speed Switch / Transmitter Operating Manual rd 3690 NW 53 Street • Fort Lauderdale, FL 33309 • Ph 954-739-4300 • Fax 954-486-4968 • www.dynalco.
TABLE OF CONTENTS 1. 2. 3. 3.1 3.2 3.2.1 3.2.2 3.2.3 3.2.4 3.3 3.3.1 3.3.2 3.3.3 3.4 3.4.1 3.5 3.5.1 4. 4.1 4.2 4.2.1 5. 6. 6.1 6.2 7. 7.1 7.2 8. 8.1 8.2 8.3 8.3.1 8.3.2 8.4 8.5 8.5.1 8.5.2 8.5.3 8.5.4 8.5.5 9. 9.1 9.1.1 9.1.2 9.2 9.2.1 9.2.2 9.3 9.3.1 9.3.2 9.3.3 9.3.4 9.3.5 9.4 9.4.1 9.4.2 9.4.3 9.5 10. 11.
Operating Instructions SWTD-1000 DYNALCO 1. Safety Instructions SWTD-1000 may only be connected by trained & competent personnel. Before opening the SWTD-1000 (Hardware configuration) the unit must be disconnected from circuits that may exhibit dangerous potentials. The instructions in this operating guide must be strictly adhered to. Not doing so may cause harm to personnel, equipment or plant.
Operating Instructions SWTD-1000 DYNALCO 3. Specifications 3.1 General SWTD-1000 Lowest measuring range Highest measuring range Minimum Measuring time (Fixtime) Effective Measuring time 0 . . . 1.000 Hz 0 . . . 35.00 kHz Selectable values: 2 / 5 / 10 / 20 / 50 / 100 / 200 / 500ms 1 / 2 / 5 Seconds. Is based on the minimum measuring time (Fixtime) and the measured frequency.
Operating Instructions SWTD-1000 DYNALCO 3.2 Inputs 3.2.1 Analog Sensor connection (Sign) Frequency range (-3dB) Input impedance Input voltage 0.01 Hz / 35 kHz 30 K • Max. 80Vrms • Max. frequency against input voltage 100 Input voltage [Veff] 10 O.K. 1 NOT O.K. 0.1 Trigger: 500mVpp Trigger: 20mVeff Minimum positive pulse width - digital signals Input voltage 100000 Frequency [Hz] 10000 1000 100 10 1 0.1 0.01 0.001 0.01 Signal voltage [Vpp] 0.5 1 2.5 5 10 20 Min.
Operating Instructions SWTD-1000 DYNALCO 3.2.2 Digital Sensor Connection (IQ) Frequency range (-3dB) Input impedance Input voltage Minimum pulse width Trigger level Screen Sensor monitoring 0.01 Hz / 35 kHz 46 K Max. ± 36V peek Min. pulse width 1.5 µs • min.Ulow = 1.6 V • max.Uhigh= 4.5 V A terminal is provided for the sensor cable screen. This terminal is connected to the sensor supply 0V.
Operating Instructions SWTD-1000 DYNALCO 3.2.4 Binary Input Use Levels Reference Max voltage Input resistance Circuit For external selection of Parameter set A or B. • Logic 1 = Parameter set A (Relay control A) • Logic 0 = Parameter set B (Relay control B) Logic 1 = V > +3.5V Logic 0 = V < +1.5V Sensor supply 0V 36V Rmin = 10KΩ Internal pull up resistance to 5V 5 volts SWTD-1000 +Bin analysis Shorting the binary input to the sensor 0V creates logic 0. parameter set A B pushbutton OVS 3.
Operating Instructions SWTD-1000 DYNALCO 3.3.2 Relay Type Limit Hysteresis Functions Accuracy Temperature tolerance Reaction time Contact rating Single Pole Double Throw Programmable – 1 lower and 1 upper set point per limit. 2 programmable parameter sets selectable via binary input • Reaction to Alarm, Sensor fault, Limit, always on or off. • “Normal“ or ”Inverse“ (normally de-enerized or energized) • With or without ‘Hold function’ (Reset via Binary input) 0.05% of the value set Max.
Operating Instructions SWTD-1000 DYNALCO 4. Principle of Operation 4.1 General The SWTD-1000 is controlled by a microprocessor. It works according to the period measurement principle whereby the input period is measured with subsequent computing of the reciprocal value corresponding to the frequency or speed. The relationship between frequency and speed is established with the Machine factor. The current output and relay control are determined from the speed.
Operating Instructions SWTD-1000 DYNALCO 4.2 Machine Factor The machine factor establishes the relationship between sensor frequency (Hz) and corresponding speed (RPM).
Operating Instructions SWTD-1000 DYNALCO 5. Installation The SWTD-1000 may only be installed by trained and competent personnel. An undamaged SWTD-1000, valid configuration and suitable installation are required. Please note the Safety Instructions in Section 1. The power to the SWTD-1000 should be capable of being disconnected via a switch or other emergency means. Before switching the equipment on the power supply voltage should be verified to be in the permissible range.
Operating Instructions SWTD-1000 DYNALCO 6.2 Terminals SWTD-1000 Sh 0VS Ana. +Vout Dig. +Bin +PO -PO NC NO Com +AO -AO Sensor connections Analog output SH 0VS +VOut Ana. Dig. +AO - AO : Screen – Sensor cable : Sensor Reference voltage : Sensor Supply : Sensor signal analog : Sensor signal digital Open Collector output +PO -PO : Open Collector Output : Signal reference for the Open Collector Gnd +24V : current positive : current negative Supply +24V Gnd : Power (10 ...
Operating Instructions SWTD-1000 DYNALCO 7. Hardware Configuration 7.1 Analog Sensor Input (Sign) J1 Jumper position J1: Sensor type J2 J2: Adaptive trigger level range 2 wire sensors (with 820Ohm Pull Up resistance) 28mV to 6.5V (>20mVrms) 3 wire and electromagnetic sensors (factory setting) 250mV to 6.5V [factory setting] (>500mVpp) 7.2 Digital Sensor Input (IQ) No hardware configuration possible or necessary.
Operating Instructions SWTD-1000 DYNALCO 8. Configuration with PC Software 8.1 Software Concept All settings are written via PC to the SWTD-1000 using the RS232 interface and the aid of the user friendly menu driven SWTD-1000 software. The parameter file may be stored, opened, printed and exchanged between the SWTD-1000 and a PC. 8.2 PC Communications Communications with the SWTD-1000 are initiated by the PC via the RS232 interface.
Operating Instructions SWTD-1000 8.4 DYNALCO Parameter List and Ranges If you already have a configuration file you can open and view it using the SWTD-1000 Windows Software menu File Æ Open You can also connect the SWTD-1000 to a PC (see section 8.2) and read back the parameters, SWTD-1000 Æ Read parameters Once loaded into the software the parameter set may be printed via File Æ Print Normal Windows file handling rules apply. Parameter list and ranges. Factory settings are shown in bold.
Operating Instructions SWTD-1000 DYNALCO 8.5 Parameters Parameters are changed in the sub menus from the drop down menu “Configuration“. Warning: New configurations only become active after being downloaded into the SWTD-1000 via: SWTD-1000 Æ Write Parameters 8.5.1 System Parameters (Configuration Æ System) Machine Factor The machine factor establishes the relationship between sensor frequency and associated speed. Machine Factor = Frequency RPM See section 4.2 Machine Factor.
Operating Instructions SWTD-1000 DYNALCO 8.5.3 Analog Output (Configuration Æ Analog Output) [mA] 21 20 4...20mA mode 12 (minimal measured value) 4 0...20mA mode 0 initial value speed [RPM] final value Measuring range – start value Analog output start value 0 or 4mA Measuring range – end value Analog output end value 20mA In the case of a negative transfer function the end value must be set smaller than the start value.
Operating Instructions SWTD-1000 DYNALCO 8.5.5 Relay Parameter and Selection of Parameter Set (Configuration Æ Relay control) Parameter set A / B selection As standard parameter set B may be activated via the binary input . If parameter set B is to be deactivated, this setting should be none (always control A) Delay time when switching A <- B This value determines the delay from switching the binary input to the switching from parameter set B to parameter set A.
Operating Instructions SWTD-1000 DYNALCO 9. Operating Behavior 9.1 9.1.1 Power On Analog Output Following power on the output assumes the output range start value. Upon completion of the first measurement the output goes to the corresponding measured value. 9.1.2 Relay Output The parameter set determined by the configuration and binary input is valid from the start.
Operating Instructions SWTD-1000 DYNALCO 9.2.2 Signal Failure In the event of a sudden loss of a good signal no positive edge arrives to complete the measurement or start a new one. Once the minimum measurement time (Fixtime) has lapsed the unit waits for twice the last measurement period following which half the last measured speed is assumed. If the signal remains missing then the measurement approaches zero following an e-function. 9.3 Functions 9.3.
Operating Instructions SWTD-1000 DYNALCO 9.3.5 Binary Input 2 functions are executable using the binary input: • Switching between parameter sets A and B. See 0 9.3.2 Parameter set A and B. • Resetting a latched relay. See 9.3.3 Relay. The binary input has an internal pull up resistor to +5V and is therefore normally logic High. 5 Volt Shorting the binary input to the sensor supply 0V creates a logic 0. +Bin 10k analysis Switching the input for between 0.1 and 0.
Operating Instructions SWTD-1000 DYNALCO 10. Mechanical Construction / Housing Mounting Terminals Sealing to EN 60925 resp. IEC 925 Dimensions Using DIN 43835 Form B clamps Detachable Terminal block. 2.5 mm 2 - Cable or 1.5 mm2 flex AWG 24 – AWG 12 UL CSA Housing IP 40 Terminals IP 20 11. Accessories Interface cable PC – SWTD-1000, Part No.