User Manual
50
Channel 24 Input Settings
Parameter Function Description Valid Inputs
110.24= Channel name for CH24
Default=” “ (blank=CH24)
11 characters (including spaces)
111.24= Units of measure for CH24
0= deg F (default)
1= deg C
2= PSI
3= PSA
4= KPA
5= FTP
6= RPM
7= “ “ (blank)
8001.24= Input type for CH24
0= J-TC (default)
1= K-TC
2= Nickel RTD
3= Platinum RTD
4= 4-20 mA (ext. resistor req’d)
5= 0-5 V
8000.24= Enables CH24 for scanning
0= disabled (default)
1= enabled
8017.24= Filter speed for CH24
Minimum=0.00 (none)
Default=0.05 (slow)
Maximum=1.00 (fast)
8012.24= Output value for 0 V or 4 mA input Minimum=-999.0
8013.24= Output value for 5 V or 20 mA input
Default= 0.0
Maximum=9999.0
(in channel units)
8015.24= Inverted resistance for 4-20mA source on CH24
Minimum=0.0 1/kohms
Default=10.0 1/kohms
Maximum=100.0 1 /kohms
8008.24= CH24 output offset to add to computed output value
Minimum=-1000.0
Default= 0.0
Maximum= 1000.0
(in channel units)
63000.24= Shutdown trip class for CH24
0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under
63001.24= Shutdown threshold value for CH24 Numeric value
63002.24= Shutdown threshold hystersis for CH24
(channel units)
63003.24=
Delay time between exceeded CH24 shutdown threshold and
CH24shutdown
seconds
63000.48= Alarm trip class for CH24
0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under
63001.48= Alarm threshold value for CH24 Numeric value
63002.48= Alarm threshold hysteresis for CH24
(channel units)
63003.48=
Delay time between exceeded CH24 alarm threshold and
CH24 alarm
seconds