Channel 23 Input Settings
Parameter Function Description Valid Inputs
110.23= Channel name for CH23
Default=” “ (blank=CH23)
11 characters (including spaces)
111.23= Units of measure for CH23
0= deg F (default)
1= deg C
2= PSI
3= PSA
4= KPA
5= FTP
6= RPM
7= “ “ (blank)
8001.23= Input type for CH23
0= J-TC (default)
1= K-TC
2= Nickel RTD
3= Platinum RTD
4= 4-20 mA (ext. resistor req’d)
5= 0-5 V
8000.23= Enables CH23 for scanning
0= disabled (default)
1= enabled
8017.23= Filter speed for CH23
Minimum=0.00 (none)
Default=0.05 (slow)
Maximum=1.00 (fast)
8012.23= Output value for 0 V or 4 mA input Minimum=-999.0
8013.23= Output value for 5 V or 20 mA input
Default= 0.0
Maximum=9999.0
(in channel units)
8015.23= Inverted resistance for 4-20mA source on CH23
Minimum=0.0 1/kohms
Default=10.0 1/kohms
Maximum=100.0 1 /kohms
8008.23= CH23 output offset to add to computed output value
Minimum=-1000.0
Default= 0.0
Maximum= 1000.0
(in channel units)
63000.23= Shutdown trip class for CH23
0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under
63001.23= Shutdown threshold value for CH23 Numeric value
63002.23= Shutdown threshold hystersis for CH23 (channel units)
63003.23=
Delay time between exceeded CH23 shutdown threshold and
CH23shutdown
seconds
63000.47= Alarm trip class for CH23
0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under
63001.47= Alarm threshold value for CH23 Numeric value
63002.47= Alarm threshold hysteresis for CH23 (channel units)
63003.47=
Delay time between exceeded CH23 alarm threshold and
CH23 alarm
seconds