User Manual

46
Channel 20 Input Settings
Parameter Function Description Valid Inputs
110.20= Channel name for CH20
Default=” “ (blank=CH20)
11 characters (including spaces)
111.20= Units of measure for CH20
0= deg F (default)
1= deg C
2= PSI
3= PSA
4= KPA
5= FTP
6= RPM
7= “ “ (blank)
8001.20= Input type for CH20
0= J-TC (default)
1= K-TC
2= Nickel RTD
3= Platinum RTD
4= 4-20 mA (ext. resistor req’d)
5= 0-5 V
8000.20= Enables CH20 for scanning
0= disabled (default)
1= enabled
8017.20= Filter speed for CH20
Minimum=0.00 (none)
Default=0.05 (slow)
Maximum=1.00 (fast)
8012.20= Display value for 0 V or 4 mA input Minimum=-999.0
8013.20= Output value for 5 V or 20 mA input
Default= 0.0
Maximum=9999.0
(in channel units)
8015.20= Inverted resistance for 4-20mA source on CH20
Minimum=0.0 1/kohms
Default=10.0 1/kohms
Maximum=100.0 1 /kohms
8008.20= CH20 output offset to add to computed output value
Minimum=-1000.0
Default= 0.0
Maximum= 1000.0
(in channel units)
63000.20= Shutdown trip class for CH20
0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under
63001.20= Shutdown threshold value for CH20 Numeric value
63002.20= Shutdown threshold hystersis for CH20
(channel units)
63003.20=
Delay time between exceeded CH20 shutdown threshold and
CH20shutdown
seconds
63000.44= Alarm trip class for CH20
0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under
63001.44= Alarm threshold value for CH20 Numeric value
63002.44= Alarm threshold hysteresis for CH20
(channel units)
63003.44=
Delay time between exceeded CH20 alarm threshold and
CH20 alarm
seconds