User Manual
30
Channel 4 Input Settings
Parameter Function Description Valid Inputs
110.4= Channel name for CH04
Default=” “ (blank=CH04)
11 characters (including spaces)
111.4= Units of measure for CH04
0= deg F (default)
1= deg C
2= PSI
3= PSA
4= KPA
5= FTP
6= RPM
7= “ “ (blank)
8001.4= Input type for CH04
0= J-TC (default)
1= K-TC
2= Nickel RTD
3= Platinum RTD
4= 4-20 mA (DIP 4 switch on)
5= 0-5 V
8000.4= Enables CH04 for scanning
0= disabled (default)
1= enabled
8017.4= Filter speed for CH04
Minimum=0.00 (none)
Default=0.05 (slow)
Maximum=1.00 (fast)
8012.4= Display value for 0 V or 4 mA input Minimum=-999.0
8013.4= Display value for 5 V or 20 mA input
Default= 0.0
Maximum=9999.0
(in channel units)
8015.4= Inverted resistance for 4-20mA source on CH04
Minimum=0.0 1/kohms
Default=10.0 1/kohms
Maximum=100.0 1 /kohms
8008.4= CH04 output offset to add to computed output value
Minimum=-1000.0
Default= 0.0
Maximum= 1000.0
(in channel units)
63000.4= Shutdown trip class for CH04
0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under
63001.4= Shutdown threshold value for CH04 Numeric value
63002.4= Shutdown threshold hystersis for CH04
(channel units)
63003.4=
Delay time between exceeded CH04 shutdown threshold and
CH04 shutdown
seconds
63000.28= Alarm trip class for CH04
0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under
63001.28= Alarm threshold value for CH04 Numeric value
63002.28= Alarm threshold hysteresis for CH04
(channel units)
63003.28=
Delay time between exceeded CH04 alarm threshold and
CH04 alarm
seconds