User Manual
25
Appendix A
This appendix contains a table of all parameter numbers found in the
SCAN2124.SPC file.
Use this appendix to keep track of the values you assign to each parameter number. The
numbers in this table are in the same order as they appear in the SCAN2124.SPC file.
Password Settings
Description
Parameter
6130=
Changes the Configuration Password
V
alid Inputs
Default=1234
"8 characters of'1'
,
'2'
,
'3'
,
or '4'"
6101= Change the time that the Configuration Password is active Minimum= 30 seconds
AFTER the user exits Configuration Mode Default= 60 seconds
Maximum=540 seconds
Trip Relay Settings
Parameter Description Valid Inputs
136=
Configure relays as inverted outputs or non-inverted
outputs
0= relay outputs non-inverted
1= relay outputs inverted (default)
63102.1= Sets trip action for user relay 1.
63102.2= Sets trip action for user relay 2.
63102.3= Sets trip action for alarm relay.
63102.4= Sets trip action for shutdown relay.
0= normally energized
1= normally de-energized
2= normally energized latching
3= normally de-energized latching
149= Selects trip action for any open thermocouple
channel
0= disabled (default)
1= alarm
2= shutdown
63050= Changes the Trip Class B timer triggered from
front-panel 'Start' key press
0= 0 minutes
1=1 minute (default)
2= 2 minutes
3= 3 minutes
4= 4 minutes
5= 5 minutes
144= Changes the Trip Class B timer time remaining
before Class B faults are displayed
0= 0 seconds
1=15 seconds
2=30 seconds (default)
3=45 seconds
4=60 seconds
5=75 seconds
6=90 seconds