User Manual

10
2.2 Wiring (Cont’d)
Connectors D and E are input terminals, each requiring p/n SC-CBLE25MM cable / terminal
block assembly.
Thermocouples can be connected to any input of either connector D or E.
For linear inputs (4 – 20 mA or 0 – 5 VDC) it is recommended to connect the wires to the
appropriate terminals for connector D. However, either connector D or E may be used. See
previous page for information on DIP switch settings for 4 – 20 mA inputs.
Any RTD inputs require the RTD module p/n SC-RTD, which includes the cable assembly. In
this case ,p/n SC-CBLE25MM will not be required. Note that (1) SC-RTD will handle up to 12
RTD inputs and can be connected to either connector D (Ch # 1 – 12) or connector E (Ch #
13 – 24).
Instructions for SC-RTD module configuration are in Appendix E.
Connector D (DB-25F)
This Connector provides the Analog Inputs for Channels 1 – 12.
Pinout:
Pin# Pin Name Pin# Pin Name
1 Channel 1 (+) 14 Channel 1 (-)
2 Channel 2 (+) 15 Channel 2 (-)
3 Channel 3 (+) 16 Channel 3 (-)
4 Channel 4 (+) 17 Channel 4 (-)
5 Channel 5 (+) 18 Channel 5 (-)
6 Channel 6 (+) 19 Channel 6 (-)
7 Channel 7 (+) 20 Channel 7 (-)
8 Channel 8 (+) 21 Channel 8 (-)
9 Channel 9 (+) 22 Channel 9 (-)
10 Channel 10 (+) 23 Channel 10 (-)
11 Channel 11 (+) 24 Channel 11 (-)
12 Channel 12 (+) 25 Channel 12 (-)