LED
Description
LED Color
LED Status
Indication
Not In Auto
Red
Solid Red
Flashing Red
A solid red illuminated LED represents
a Not in Auto condition.
A flashing red illuminated LED means
the GSC400 is in OFF – sleep mode.
Low Coolant
Red
Amber
Solid Red
Solid
Amber
A solid red illuminated LED represents
a Low Coolant (Temperature and/or
Level) failure condition.
A solid yellow illuminated LED
represents a Low Coolant
Temperature Warning condition
Pre-Heat
Green
Solid
Green
A solid green illuminated LED
represents an active Pre-Heat
condition.
EPS
Supplying
Load
Green
Red
Solid
Green
Solid Red
A solid green illuminated LED
indicates that the generator is
supplying load.
A solid red indicates load is detected
on the generator when none should
be. This is only supported if using
the EPS supplying load configurable
switched input feature.
Failure
Red
Solid Red
A solid red illuminated LED represents
a general Failure condition.