OPEN AUX ANALOG 2
voltage. Could indicate that the sender is not
connected to the analog input (i.e. broken wire).
OPEN ENG TEMP
OPEN ENGINE TEMP
OPEN FUEL BASIN
OPEN FUEL LEVEL
OPEN OIL LEVEL
OPEN OIL PRES
OVER CRANK
The GSC400 could not start the generator. See
section 3.3 (engine logic) on page 47 and section
3.5 (speed sensing) on page 55.
OVER CURRENT
Over current failure. See section 3.7.3 on page
62.
OVER FREQUENCY
Generator Frequency over the failure threshold.
See section 3.7.1 on page 58.
OVER SPEED
Generator RPM too high. See section 3.5 on
page 55.
OVER VOLTAGE
Generator voltage high. See section 3.7.2 on
page 58.
POWER ON*
GSC400 was powered up from unpowered state.
RECOVERY
Software in the GSC400 encountered a problem
and had to perform an automatic recovery. If this
occurs, record the numbers displayed and
contact Dynagen.
REMOTE START*
The GSC400 was started / stopped from the
remote start contacts.
REMOTE STOP*
RS232 FAILURE
These are internal GSC400 failures. Try power
cycle the GSC400. If the failure occurs
repeatedly the unit could be defected.
RS485 FAILURE
SHORT AUX ANALOG 1
Analog sender reads zero volts or close to zero.
This could be caused by a shorted sender.
SHORT AUX ANALOG 2
SHORT ENG TEMP
SHORT ENGINE TEMP
SHORT FUEL BASIN
SHORT FUEL LEVEL
SHORT OIL LEVEL
SHORT OIL PRES
TLE6230 FAILURE
This is an internal GSC400 failure. Try power
cycling the GSC400. If the failure occurs
repeatedly the unit could be defected.
UNDER FREQUENCY
The generator frequency is too low. See section
3.7.1 on page 58.
UNDER SPEED
The engine speed is too low. See section 3.5 on
page 55.
UNDER VOLTAGE
The generator output voltage is too low. See
section 3.7.2 on page 58.