User manual
93 of 148
INITIALIZING*
EEPROM is being loaded with factory defaults.
This occurs on first power up or if the user resets
the GSC400 to factory defaults from the PC
Configurator.
KEY BOARD FAILURE
This is an internal GSC400 failure. Try to power
cycle the GSC400. If the failure occurs
repeatedly the unit could be defected.
LOCKED ROTOR
Cranking attempt failed on locked rotor. See
section 3.3.1.1 on page 48.
LOG CORRUPTED
Event Log corrupted and had to be reset. This
usually occurs when power was loss while the
event log was being written to. It will also occur
when upgrading firmware to version 2.00 or
higher from a version below 2.00 for the first
time.
LOSS OF ECM COMM
J1939 messages required by the GSC400 have
not been received. The generator has shut
down. See section 3.8 on page 63.
LOW AIR PRESSURE
The low air pressure switched input is active.
See Table 17 on page 67.
LOW AUX AN1
The Auxiliary Analog 1 / 2 analog input is below
the low failure setpoint. The Auxiliary Analog 1
and 2 can be programmed with custom text so
the text to the left may not apply.
LOW AUX AN2
LOW BATTERY
Low battery voltage failure. See section 3.6 on
page 50.
LOW COOLANT [Level]
Low coolant level switched input failure. See
Table 17 on page 67.
LOW FUEL LEVEL
Failure due to low fuel. See section 3.4 on page
50.
LOW HYDRAULIC
Low Hydraulic digital input was active. See
Table 17 on page 67.
LOW OIL LEVEL
See section 3.4 on page 50.
LOW OIL PRESSURE
See section 3.4 on page 50.
MAINTENANCE
NEEDED*
The generator requires maintenance. See
section 3.13 on page 74.
MAINTENANCE
PERFORMED*
Maintenance has been performed on the
generator (i.e. the maintenance timer has been
reset). See section 3.13 on page 74.
MANUAL START*
Generator started manually from the front panel
RUN key.
MANUAL STOP*
Generator stopped manually from the front panel
OFF key.
OFF ENABLE*
Front panel OFF key pressed to disable
automatic starting.
OPEN AUX ANALOG 1
Analog sender always reads the maximum