3.16.2 LCD Heater
There is an option for an LCD heater that allows the LCD display to operate
normally down to -40
0
C (for more information contact Dynagen).
There is an option in the “Other Setting” menu called “LCD Heater” that allows
the heater to be enabled or disabled. It is set to disabled by default.
3.16.3 Fan Control
The fan control is meant to operate in conjunction with the engine run
configurable output. The fan control also has a “fan control” configurable output
that must be set.
Figure 12 (below) and Table 19 (below) describe its logic.
Figure 12 – Fan Control Logic
“High Fan
On” Setting
crank
success
“Fan Switch
Dly” Setting
“High Fan On”
Setting – 5
0
C
GSC400 Engine
Temperature
Time
“Fan Switch
Dly” Setting
Fan Output on
Fan Output off
Fan Output off
Fan
Output
off
Engine Run output on
Engine Run output off