Figure 11 – Example of Common Fault 1 Usage
3.16 Other Setting
The Other Setting menu contains the settings used to control the features in the
following sections.
3.16.1 Dummy Load
The dummy load feature allows the user to turn on an output if the AC current is
below a settable threshold (Load On Point). This is useful for applications
where the generator must have a minimal load to prevent damage to the
generator.
Upon crank success (RUN Mode entered), if enabled, the feature waits for a
configurable bypass time, then starts to monitor the AC current. If the AC current
remains below the Load On Point for 6.5 seconds then the dummy load
configurable output is turned on. If the AC current rises and remains above a
settable threshold (Load Off Point) for 1.5s, the dummy load configurable output
is turned off.
A digital output must be set to dummy load to use this feature.