User manual
70 of 148
Over RPM Warning
[Over Speed Warning]
This turns on the digital output if the Over Speed Warning is
activated. See section 3.5 for more details.
Low Fuel Failure
This turns on the digital output if the Low Fuel Failure is
activated. See section 3.4 for more details.
Low Fuel Warning
This turns on the digital output if the Low Fuel Warning is
activated. See section 3.4 for more details.
Battery Failure
This turns on the digital output if the Low or High Battery
Failure is activated. See section 3.6 for more details.
Battery Warning
This turns on the digital output if the Low or High Battery
Warning is activated. See section 3.6 for more details.
Low Coolant [Level]
Failure
This turns on the digital output if the Low Coolant Level
Failure is activated. This is controlled by the Low Coolant
Level Digital Input described in Table 17 in section 3.9.
Low Coolant [Level]
Warning
Reserved for future use. Selecting this feature will have no
effect.
Not In Auto
This turns on the digital output when the controller is not in
the Auto state. Section 4.4 describes the various states of
the controller.
General Failure
This turns on the digital output when any failure is active.
Crank Rest
This turns on the digital output when the controller is in the
crank rest state after a crank attempt. The crank rest
duration is set in the engine logic menu. See section 3.3.1
for more details.
Engine Running
This turns on the digital output when the controller enters
the run state (crank success). The run state is described in
section 4.4.4.
Engine Cranking
This turns on the digital output when the crank output is on.
See section 3.3.1 for more details.
Exerciser Alarm
This turns on the digital output when the engine/generator
starts on an exerciser event (section 3.11).
Battery Recharge Alarm
This turns on the digital output when the engine/generator
starts on a low battery event (section 3.6).
Under Voltage Warning
This turns on the digital output when the AC Under Voltage
Warning (section 3.7.2) is activated.
Over Voltage Warning
This turns on the digital output when the AC Over Voltage
Warning (section 3.7.2) is activated.
Over Current Warning
This turns on the digital output when the AC Over Current
Warning (section 3.7.3) is activated.
Fuel In Basin Warning
This turns on the digital output if the Low Fuel In Basin
Warning (section 3.4) is activated.
Voltage Regulator
This allows the digital output to be controlled by the idle
feature. The idle feature also requires a digital input to be
set to Idle Mode (see section 3.9). See section 2.13 on
page 40 for more information on the Idle Mode feature.
On when the fuel relay turns on and off when fuel relay turns
off. Following exceptions:
(1) Does not turn off during crank rest if fuel turns off
(2) Off during idle mode.
Low Temperature
This turns on the digital output if the Low Engine