3.10 Digital Outputs (Configurable Outputs) Setup
There are eight 200mA configurable outputs (all switched to ground) and one
40A digital output (dry contact), the Extra Relay output, all of which are
configurable. Each feature (listed in Table 18 below) is permitted to be set to
only one configurable output.
Table 18 – Configurable Output Selections
Name
Description
Warm Up
This sets up the output to be controlled by the Warm-up
feature. See section 3.3.1 for more details. The Warm-up
time is set in the engine logic menu. This is an active low
output (i.e. the output remains off during warm-up and turns
on after warm-up is finished). The output always remains off
when the controller is not in the RUN mode.
Energize to Stop (ETS)
This allows the Energize to Stop feature to control an output.
The time duration is set in the engine logic menu. See
section 3.3.2 for more details.
Preheat (glow plug)
This allows the Preheat, Midheat, and Postheat features in
the engine logic menu to control the output. The Preheat
(glow plug) time is set in the engine logic menu. See
section 3.3.1 for more details.
Cool Down
This allows the Cool Down feature to control the output.
This output is active during cool down. The Cool Down
duration is set in the engine logic menu. See section 3.3.2
for more details.
Over Crank
This turns on the digital output when the Over Crank Failure
is activated. See section 3.3.1 for more details. The
number of crank attempts is set in the engine logic menu.
High Temp Failure
This turns on the digital output if the High Engine
Temperature Failure is activated. See section 3.4 for
more details.
High Temp Warning
This turns on the digital output if the High Engine
Temperature Warning is activated. See section 3.4 for
more details.
Low Oil Failure
This turns on the digital output if the Low Oil Pressure
Failure is active. This can be caused by the Low Oil
Pressure Analog Input or the Low Oil Pressure digital input.
See section 3.4 or section 3.9 for more details.
Low Oil Warning
This turns on the digital output if the Low Oil Pressure
Warning is activated. See section 3.4 for more details.
Under RPM Failure
[Under Speed Failure]
This turns on the digital output if the Under Speed Failure is
activated. See section 3.5 for more details.
Under RPM Warning
[Under Speed Warning]
This turns on the digital output if the Under Speed Warning
is activated. See section 3.5 for more details.
Over RPM Failure [Over
Speed Failure]
This turns on the digital output if the Over Speed Failure is
activated. See section 3.5 for more details.