User manual

68 of 148
Running” is displayed on the GSC400 display when this
input is active.
The idle mode can also turn on a configurable output (see
the Voltage Regulator configurable output feature in Table
18 on page 69). This output is usually used to turn off the
generator voltage regulator when idle mode is entered but
can be used for any purpose.
This is also used for Cummins J1939 Idle Feature. See
section 3.8.3 on page 66 for more information.
Start / Stop
When the digital input is active the generator is started if in
the Auto mode. If the digital input becomes inactive this
places the controller back into the Auto mode (shuts down
the generator). This performs the same function as the
remote start contacts.
Auxiliary Failure
An Auxiliary Failure is generated when the input is active.
This can occur in the Off, Auto, Cranking, and Running
states.
Auxiliary Warning
An Auxiliary Warning is generated when the input is active.
This can occur in the Off, Auto, Cranking, and Running
states.
Charger 1 Fault
A Charger 1 Fault warning is generated when the input is
active.
Charger 2 Fault
A Charger 2 Fault warning is generated when the input is
active.
High Fuel Level Warning
A “High Fuel Level Warning” is generated when the input is
active.
Config Warn 1
These inputs when active generate a warning/failure and a
configurable text message is displayed to the screen when
the input is active. The text message can only be
configured from the GSC400 PC Interface. The length of
the message is limited to 15 characters.
The user can control the states in which these features are
enabled. The selections are:
1. Global –Everywhere
2. Crank – From start of delay-to-start to the end of
cranking
3. Run – RUN Mode only
4. Crank+Run – Combination of 2 and 3 above.
These settings are located at the bottom of the menu for
each input.
Config Warn 2
Config Fail 1
Config Fail 2
Start Inhibit
When inactive this prevents a manual or automatic start.