3.7.2.1 Voltage Select Inputs
You can choose a voltage configuration by setting one or two of the configurable
switched inputs to Volt Select 1 and Volt Select 2. This allows the GSC400 to
automatically re-configure its voltage display as well as warning/shutdown trip
points relating to AC voltages and currents. This is useful for mobile generators
where the voltage selections can be selected via a CAM switch.
Warning: The Voltage Select Inputs override the Voltage Group parameter.
Table 14 Voltage Select Inputs
Voltage Configuration
Switched Inputs
Volt Select 1
Volt Select 2
Voltage Group 1
(Single Phase)
1 Phase, 3-wire (2-wire
option also selectable)
Open Circuit
Open Circuit
Voltage Group 2
3 Phase, 4-wire Wye,
ungrounded delta
ACTIVEP
P
Open Circuit
Voltage Group 3
3 Phase, 4-wire Wye,
ungrounded Delta
(2x display voltage option
also selectable)
Open Circuit
ACTIVEP
P
Voltage Group 4
3 Phase, 4-wire Wye,
ungrounded Delta
(4-wire, corner grounded,
Delta option also selectable)
ACTIVEP
P
ACTIVEP
P
P
P
If Digital Input Pin A, B, C or D is used, then ACTIVE is defined as a switched
to +BAT connection. If Digital Input Pin E, F, G or H is used, then ACTIVE is
defined as a switched to GND connection.
NOTE: If only a single AC Group Sel function is selected, then the remaining
unassigned AC Group Sel is equivalent to an “Open Circuit” in the above table.