If you are satisfied with the selection then you must highlight the selection
and then press enter. You will then be taken back to the previous menu.
If there is no checkmark you must make a selection. See the next bullet
point.
If you wish to make another selection scroll down to the desired selection
and press enter. A checkmark should appear beside the option selected.
Then – with the desired option still selected – press enter again to exit the
menu.
3.2 Advanced Setup Menu Overview
Table 6 – Advanced Menu Layout Summary
Advanced Menu Layout
Description
Section
(Page)
J1939 Setup
The J1939 setup contains general
settings for J1939 such as shutdown on
loss of messages. To read parameters
from the J1939 bus please see “Analog
Inputs” below.
3.8 (63)
High Engine Temp
Sensor Inputs:
These control all aspects of the specific
analog input listed in the left column such
as whether it is a switch, sender, or
obtained from J1939. You can also set
the input you want it to connect to. The
warnings and failures as well as open and
shorted sender detection shutdowns are
also configurable.
3.4 (50)
Oil Pressure
Fuel Level
Oil Level
Fuel In Basin
Low Engine Tmp
Speed Sensing
The speed sensing source (magnetic
pickup, generator voltage, J1939), under
and over speed warnings and failures.
3.5 (55)
AC Frequency
The crank disconnect frequency and the
over/under frequency warning/failures.
3.7 (58)
AC Voltage
The AC voltage sensing/display is
contained here as well as the over and
under voltage warnings and failures.
AC Current
The CT ratio, AC current sensing and
display enable are contained in this
menu.
Engine Logic
All the basic start and shutdown logic are
contained in this menu.
3.3 (47)
Outputs Setup (i.e.
Configurable Outputs)
This menu allows you to assign a
feature/action to one of eight configurable
outputs. For example you can turn on an
output when an under-speed failure
3.10 (69)