UGSC400 Specifications
VDC Rating
12/24 VDC
Standby Current
50 mA @ 12 VDC
Operating Temp
-40°C to +70°C (-40°F to +158°F)
LCD Operating
Temp***
-20P
0
P
C to 70P
0
P
C (-4P
0
P
F to +158P
0
P
F)
-40
0
C to +70
0
C (-40
0
F to +158
0
F) with heater “-H” option (consult factory)
Function
Selection
Range
Function
Range
Speed Sensing
0-300vac, 0-3600rpm
0-300vac, 0-3600rpm
Voltage Sensing
70 - 346vac L-N (600V L-L, L-
L calculated from L-N)
Accuracy: +/- 1% L-N Full
Scale
Current Sensing*
Max 5A, +/- 2% Full Scale
Harmonics present on the AC lines cannot exceed 260Hz. VFD (Variable
Frequency Drive) devices often cause harmonics that exceed this value.
Frequency Sensing
1 – 100 HZ
Engine Temp
Depends on sender.
Oil Pressure
Depends on sender.
Oil Level
0-100% Depends on sender.
Fuel Level
0-100% Depends on sender.
Engine Logic
0 – 60 seconds
0 – 60 seconds
3 – 60 seconds
1 – 60 seconds
0 – 60 seconds
1 – 60 tries
Enable, Disabled
0 – 60 seconds
0 – 600 seconds
0-600 seconds
0-700 PSI
100-2000 RPM
Analog Input
Gnd=Fail, Open=fail, 7mA
Max
Note: On LS/LX controllers
Input 2 is High Z, Gain = 3
and Input 6 has a gain of 3.
Digital Input
Bat=Fail, 7mA Max
Gnd=Fail, 7mA Max
Digital Output
200 mA Max
40A Max
Exerciser
10-240 Minutes
Battery Recharge
10-240 Minutes
Password
0-9
LCD Display
128x64 Graphic display, Backlit, 60° viewing angle
LED Display
Red, Green, Yellow LED representation, Daytime Visible, 60° viewing angle
Programming
Manual, Software, Field upgradeable
J1939 Interface
Low emission capable
Relays**
Replaceable 40A relays for Crank, Fuel, Extra output. 12 or 24VDC Coil
Dimensions
W x H x D, 139 x 113 x 65 mm (5.47 x 4.45 x 2.56 in.)
Weight
0.45 Kg (1.0 Lb)
t
Voltage measured L-N. L-L is calculated. *Use of Industry Standard CT Required. ** 40A output at
room temperature. *** The LCD display will exhibit color and response time changes at high and low
temperatures respectively but will not be damaged as long as within Operating Temp.