2.10.1 Timed Output on Failure Shutdown
If you wish to provide a timed output when the engine shuts down you can do the
following.
1. Set the “Energized to Stop” feature to one of the Switched Inputs A to H.
2. Set the “Energized to Stop” duration in the Engine Logic menu to the
duration you wish to time the configurable output.
3. Set the desired Configurable Output you wish to have timed. Only failures
are valid.
Wire the GSC400 as shown below.
Figure 9 – Timed Configurable Output on Engine Shutdown