Emergency Stop Input
Pin 9 of the configurable switched input connector must be grounded (can use
pins 11 or 12) to disable the emergency stop feature. When enabled the
emergency stop feature forces the controller to remain in the OFF mode and
sounds the buzzer.
Remote Start Contacts (RSC)
A normally open switch needs to be placed across pin 10 of the configurable
switch input connector and ground (pin 11 or 12 on the same connector can be
used for convenience). When the switch closes the GSC400 will start the genset
if in AUTO. When the switch opens the GSC400 will stop the genset.
The wiring for the RSC should be specified assuming a maximum 0.5A current
draw on the lines.
LCD Heater (GSC400-H versions only)
If you have a unit with an LCD heater you must enable it. See section 3.16.2 on
page 76.