User manual
19 of 148
Digital
Outputs*
Terminal
Detail
Terminal
Location
Wire Size
(AWG)
Current
max.
Function
+ V Bat
1
18
1.5A
Battery +
Output A
2
18
200mA
These are sinking outputs
(i.e. switched to ground).
Output B
3
18
200mA
Output C
4
18
200mA
Output D
5
18
200mA
Output E
6
18
200mA
Output F
7
18
200mA
Output G
8
18
200mA
Output H
9
18
200mA
+ V Bat
10
18
1.5A
Battery +
RS485
(Modbus)
Terminal
Detail
Terminal
Location
Wire Size
(AWG)
Current
max.
Function
RS485-A (+)
1
18
7mA
RS485 High
Ground
2
18
7mA
RS485 Common
RS485-B (-)
3
18
7mA
RS485 Low
RS485-A (+)
4
18
7mA
RS485 High
Ground
5
18
7mA
RS485 Common
RS485-B (-)
6
18
7mA
RS485 Low
AC Voltage
Sensing
Terminal
Wire Size
(AWG)
Current
max.
Function
Phase A*
18
7mA
Monitor Generated AC Voltage
Phase B*
18
7mA
Phase C*
18
7mA
Neutral
18
7mA
AC Voltage Neutral connection
AC Current
Sensing
Terminal
Detail
Terminal
Location
Wire Size
(AWG)
Current
max.
Function
Phase A -
1
18
5A
Current Transformer
connections.
Phase B -
2
18
5A
Phase C -
3
18
5A
Phase A +
4
18
5A
Phase B +
5
18
5A
Phase C +
6
18
5A
J1939
(CAN)
Terminal
Detail
Terminal
Location
Wire Size
(AWG)
Current
max.
Function
CANH
1
18
7mA
CANH Connection
Ground
2
18
7mA
Not Needed
CANL
3
18
7mA
CANL Connection
Ground
4
18
7mA
Not Needed