User manual

18 of 148
Table 2 – GSC400 Terminal Details
PC Config
This is a 10 pin (2x5) connector for the connection of the GSC400
programmer only. This connector is not meant for long term connections
under vibration.
Quick Fit
Terminals
Terminal
Wire Size
(AWG)
Current
max.*
Function
Crank
12
40A at
12VDC,
20A at
24VDC
Crank Output Terminal
Battery +P (x 2)
12
Positive Battery Terminal
Battery -P (x 2)
12
Negative Battery Terminal
Fuel
12
Fuel Output Terminal
Extra Relay 1 / 2
12
Extra Relay Dry Contact
Speed 1 / 2
18
100mA
Speed Signal Connection
*Total controller current output (max 60A at 12VDC, 30A at 24VDC)
P
Analog
Inputs
Terminal
Detail
Terminal
Location
Wire
Size
(AWG)
Current
max.
Function
Ground
1
18
7mA
Ground
Input 2
2
18
7mA
Low Ohms, Gain of 1*
Input 3
3
18
7mA
Low Ohms, Gain of 3
Input 4
4
18
7mA
Low Ohms, Gain of 3
Input 5
5
18
7mA
High Ohms, Gain of 3
Input 6
6
18
7mA
High Ohms, Gain of 1 **
Input 7
7
18
7mA
High Ohms, Gain of 3
5V out ***
8
18
7mA
5V Power output ***
* LSB/LXB controllers only. For LS/LX controllers, this input spec is High
Ohms, Gain of 3. ** LSB/LXB controllers only. For LS/LX controllers this
input has a gain of 3. *** LSB/LXB controllers only. For LS/LX controllers
this terminal is a ground.
Digital
Inputs
Terminal
Detail
Terminal
Location
Wire
Size
(AWG)
Current
max.
Function
Input H
1
18
7mA
Active = Battery -
Input G
2
18
7mA
Active = Battery -
Input F
3
18
7mA
Active = Battery -
Input E
4
18
7mA
Active = Battery -
Input D
5
18
7mA
Active = Battery +
Input C
6
18
7mA
Active = Battery +
Input B
7
18
7mA
Active = Battery +
Input A
8
18
7mA
Active = Battery +
Emer. Stop
9
18
7mA
Open = Active,
Battery - = Inactive
Remote
Start
10
18
7mA
Battery - = Start,
Open = Stop
Ground
11
18
7mA
Battery - reference
Ground
12
18
7mA
Battery - reference