User manual

143 of 148
63 MODBUS START
162 (0xA2) CONFIG FAIL 1
163 (0xA3) CONFIG FAIL 2
176 OPEN AUX ANALOG 1
177 SHORT AUX ANALOG 1
178 LOW AUX ANALOG 1
179 HIGH AUX ANALOG 1
180 OPEN AUX ANALOG 2
181 SHORT AUX ANALOG 2
182 LOW AUX ANALOG 2
183 HIGH AUX ANALOG 2
233 (0xE9) DTC
235 (0xEB) System Recovery
40132
Log Time stamp
Minutes
Decimal
0 ~ 59
R
Decimal format
High 4-bit tens 0 ~ 5
Low 4-bit ones 0 ~ 9
Minute
40133
Log Time stamp
Hours
Decimal
0 ~ 23
Decimal format
High 4-bit tens 0 ~ 2
Low 4-bit ones 0 ~ 9
Hour
40134
Log Time stamp
Date
Decimal
1 ~ 31
Decimal format
High 4-bit tens 0 ~ 3
Low 4-bit ones 0 ~ 9
Day
40135
Log Time stamp
Month
Decimal
1 ~ 12
Decimal format
High 4-bit tens 0 ~ 1
Low 4-bit ones 0 ~ 9
Month
40136
Log DTC code.
Only valid if entry
contains DTC
message (if Log
Type register
40131 equals 233).
0 ~ 255
R
Lowest byte of SPN (bit 8 MSB)
40137
0 ~ 39
Middle byte of SPN (bit 8 MSB)
40138
0 ~ 31
3 highest bits of SPN and the FMI (bit
8 is SPN MSB and bit 5 is FMI MSB)
40139
Bit 8 CM, other 7 bits OC (bit 7 MSB)
40140
Log Sequence
1 ~ 100
R
Current log being read.
40141
Total Log Number
1 ~ 100
R
Total number of entries in the log.