User manual

141 of 148
40148
Auxiliary Analog 2
Type
0 - 6
R
0 = not available
1 = set to a switch
2 = Temperature in 0F
3 = Temperature in 0C
4 = Pressure in PSI
5 = Pressure in kPa
6 = Level (%)
40149
Auxiliary Analog 2
Value
0 – 999.9
R
1 bit equal 0.1 unit
Reading 1000
corresponds to
100.0
Units depends on
the Type above.
2. EVENTS HISTORY LOG
40130
Read Previous
Entry
0x6C93
(27795)
W
Write control command to holding
register address.
Read Next Entry
0x639C
(25500)
W
The controller will check the log request every 1 second. Each time a new command is
received, the controller will scroll either down or up one message (until it reaches either the
bottom or top of the message log), one message and update the log content in address
40131 to 40141. Once at the top of the log, registers 40131 to 40141 are not changed if a
“Read Previous Entry” command is received. Once at the bottom of the log, registers 40131
to 40141 are not changed if a “Read Next Entry” command is received. After 20s of
receiving further commands in register 40130, all registers are cleared (i.e. set to 0).
40131
Log Type
Only
supports the
values listed
in format
column.
R
1 Internal reserved 1 ( ADE Read )
2 Internal reserved 2 ( KEYBOARD)
3 Internal reserved 3 ( ADC read )
4 Internal reserved 4 ( RS485 )
5 Internal reserved 5 ( RS232 )
6 Internal reserved 6 ( ADE Write )
7 Internal reserved 7 ( TLE6230 )
8 Internal reserved 8 ( EEPROM )
9 (Reserved).
10 HIGH ENGINE TEMPERATURE
11 LOW OIL PRESSURE
12 UNDER SPEED
13 OVER SPEED
14 LOW FUEL LEVEL
15 LOW BATTERY