User manual

140 of 148
40176
Current Run time
(Total run time on active
running event).
NOTE: Timer is reset to
Zero after active
running event has been
terminated (OFF or
AUTO mode waiting to
start)
0 ~ 6553.5
R
1 bit 0.1 hour
65535 corresponds to
6553.5Hs
Hours
40177 ~
40178
Engine Hours (old
way – use registers
40172/40173
instead)
0~255999.9
R
Total Accumulated
running hours, the
reading in 40177, 1 bit
equal to 0.1 hour. The
reading in 40178, 1 bit
equal to 1000 hours. So
the total hours = 40178
* 1000 + 40177/10
Hours
40145
Maintenance Time
-1000 ~
+1000
Signed Integer
16 bit
R
The unit is 0.1 hour (1 bit = 0.1 hour);
Positive values count down the hours
to next maintenance. Negative values
count up the hours since
maintenance should have been
performed. Positive or negative
values can be identified by read the
high byte of MSB. A 1 in bit 15
corresponds to a negative number
while a 0 corresponds to a positive
number.
40146
Auxiliary Analog 1
Type
0 - 6
R
0 = not available
1 = set to a switch
2 = Temperature in
0
F
3 = Temperature in
0
C
4 = Pressure in PSI
5 = Pressure in kPa
6 = Level (%)
40147
Auxiliary Analog 1
Value
0 – 999.9
R
1 bit equal 0.1 unit
Reading 1000
corresponds to
100.0
Units depends on
the Type above.