User manual
138 of 148
Bit2 = Output C 0 = OFF, 1 = ACTIVE
Bit3 = Output D 0 = OFF, 1 = ACTIVE
Bit4 = Output E 0 = OFF, 1 = ACTIVE
Bit5 = Output F 0 = OFF, 1 = ACTIVE
Bit6 = Output G 0 = OFF, 1 = ACTIVE
Bit7 = Output H 0 = OFF, 1 = ACTIVE
Bit8 = Extra Relay 0 = OFF, 1 = ACTIVE
Bit9 = Fuel Relay 0 = OFF, 1 = ACTIVE
Bit10 = Crank Rly 0 = OFF, 1 = ACTIVE
Advanced Modbus register support
1. ENGINE-GENERATOR PARAMETERS
(Read Only)
Running parameters will update every 1 second. The engine speed, high engine
temperature, low engine temperature, oil pressure, and fuel level parameters display
0xFF01 if not available (if source is J1939). The six sender inputs (High Engine
Temperature, Low Engine Temperature, Fuel Level, Oil Pressure, Oil Level, and Fuel In
Basin) parameters display 0xFF00 if set to switch or disabled.
40150
Engine Speed
0 ~ 6553.0
R
1 bit equal 0.1 RPM
Reading 18000
corresponds to
1800RPM
RPM
40151
High Engine
Temperature
0 ~ 250.0
R
1 bit equal 0.1 unit
Reading 1000
corresponds to 100.0C
C
40153
Low Engine
Temperature
0 ~ 250.0
R
1 bit equal 0.1 unit
Reading 1000
corresponds to 100.0C
C
40154
Fuel Level
0.0 ~ 100.0
R
1 bit equal to 0.1%
Reading 1000
corresponds to 100.0%
%
40155
Oil Pressure
0.0 ~
1000.0
R
1 bit equal 0.1 unit
Reading 1000
corresponds to
KPa