User manual

136 of 148
32 OPEN FUEL LEVEL
33 SHORT FUEL LEVEL
34 OPEN OIL LEVEL
35 SHORT OIL LEVEL
36 OPEN FUEL BASIN
37 SHORT FUEL BASIN
40 AUXILIARY FAIL
41 UNDER FREQUENCY
42 OVER FREQUENCY
162 USER CONFIG FAIL 1
163 USER CONFIG FAIL 2
176 OPEN AUX ANALOG 1
177 SHORT AUX ANALOG 1
178 LOW AUX ANALOG 1
179 HIGH AUX ANALOG 1
180 OPEN AUX ANALOG 2
181 SHORT AUX ANALOG 2
182 LOW AUX ANALOG 2
183 HIGH AUX ANALOG 2
255 (0xFF) Empty – No failure message
40109
System Sub-state
delay countdown
0 ~ 65535
R
The value of register 40109
corresponds to the count down delay for
one of the below mentioned sub-states.
To determine which sub-state is in
countdown mode read register 40101.
Resolution is 1 second.
The following sub-states incorporate
delay countdown:
DLY TO START
PREHEATING
CRANKING
WARMUP
CRANK REST
COOLDOWN
IDLE COOL (COOLDOWN IN IDLE)
LOW BATTERY PRELARM
LOW DC BATTERY CHARGING
EXERCISER PREALARM
EXERCISER RUNNING