User manual
135 of 148
81 HIGH AUX ANALOG 2 warning
255 (0xFF) Empty – No message in
queue
40108
Active Failure
0 ~ 44
R (Read
Only)
If the controller is in an active FAILURE
mode the failure number in register
40108 corresponds to the below failure
mode.
0 reserved
1 Internal reserved 1 ( ADE Read )
2 Internal reserved 2 ( KEYBOARD )
3 Internal reserved 3 ( ADC read )
4 Internal reserved 4 ( RS485 )
5 Internal reserved 5 ( RS232 )
6 Internal reserved 6 ( ADE Write )
7 Internal reserved 7 ( TLE6230 )
8 Internal reserved 8 ( EEPROM )
9 (Reserved )
10 HIGH ENGINE TEMP
11 LOW OIL PRESSURE
12 UNDER SPEED
13 OVER SPEED
14 LOW FUEL LEVEL
15 LOW BATTERY
16 LOW COOLANT
17 OVER CRANK
18 OVER VOLTAGE
19 UNDER VOLTAGE
20 OVER CURRENT
21 EPS LOADS ERROR
22 LOW AIR PRESSURE
23 LOW HYDRAULIC
24 LOW OIL LEVEL
25 LOCKED ROTOR
26 HIGH BATTERY
27 LOSS OF ECM COMMUNICATION
28 OPEN ENG TEMP (applies to both
High and Low Engine Temperature)
29 SHORT ENG TEMP (applies to both
High and Low Engine Temperature)
30 OPEN OIL PRES
31 SHORT OIL PRES