36 EXERCISER RUNNING
0 None of the above. 0 corresponds to
none of the above sub modes of
operation.
40102
~
40107
Active Event
message queue
0 ~ 255
R (Read
Only)
A maximum of 6 events/warnings are
stored concurrently. One event/warning
per register. Ensure that controller is
not in sleep mode before reading.
0 READING ABORT (DTC reading)
1 Low Voltage In Crank
2 Charger 1 Fault
3 Need Maintenance
4 CRANK FAILURE
5 Charger 2 Fault
6 Custom Warning 1
7 Custom Warning 2
8 CRANK SUCCESS
9 Empty Space
11 REQUESTING DTC
14 LAMP TEST
15 High Fuel Level
16 Warning
17 Low AC Voltage
18 Over Cur Latched
19 ↑+↓ FOR UNLATCH
20 READ DTC SUCCESS
21 FUEL OFF – If fuel turned off during
crank rest.
22 Low Engine RPM
23 High Engine RPM
24 High AC Current
25 High AC Voltage
26 High Engine Temp
27 Low Oil Pressure
28 Low Fuel Level
29 EXERCISE Prealarm
30 CHARGE Prealarm
31 NO DTC AVAILABLE
32 DM2 REQUEST FAIL
33 KEEP FUELING – If fuel remains on
during crank rest.