User manual

131 of 148
40095 LSB = NOT USED
2. START/STOP CONTROL AND COMMAND
Start/Stop registers are polled by the controller every 250mS.
40098
SYSTEM DISABLE
0x5DA2
(23970)
W
When 0x5DA2 is written to address
40098 this places the controller in the
OFF mode (System disabled). The
register is read in all controller
operating modes (Running, Auto,
Failure, Menu/sleep modes).
CAUTION – when received in the
Running mode the controller
immediately goes to the OFF mode
(no cool-down is performed). When
received in failure mode this will
reset the system failure and revert
to the OFF mode.
SYSTEM ENABLE
0x5BA4
(23460)
W
When 0x5BA4 is written to address
40098 this places the controller in the
AUTO mode (waiting to start). The
register is read only in the OFF
mode of operation and ignored in
all other operating modes.
START
0x9768
(38760)
W
When 0x9768 is written to address
40098 this initiates an automatic start.
This register is only read in the
AUTO mode of operation and is
ignored in other modes.
STOP
0x57A8
(22440)
W
When 0x57A8 is written to address
40098 this initiates a shutdown/stop
of the equipment. This register is only
monitored when the system is
running (start signal received) and is
ignored in all other operating modes.
When cool down is enabled and a
stop command is received the
controller will proceed to the cool
down mode then shutdown
equipment.