User manual

128 of 148
40081
bit0: EPS supplying load shutdown
(red) bit1: EPS supplying load (green)
bit2: not used
bit3 : Glow plug on (green)
bit4 : Failure is active (Red Failure
LED)
bit5 to bit7: (not used)
bit8: Crank relay On (no LED)
bit9: Fuel relay ON (no LED)
bit10: Extra relay ON (no LED)
bit11 to bit13: (Reserved)
bit14 and bit 15: (not used)
40082
Events / Warnings
Status
0 = OFF,
1 = ON
R
bit0 : Warm up finished
bit1 : ETS is on
bit2 : Glow plug is on
bit3 : Cool Down is active
bit4 : Over crank occurred
bit5 : High engine temperature failure
bit6 : High engine temperature
warning
bit7 : Low oil pressure failure
bit8 : Low oil pressure warning
bit9 : Under speed failure
bit10: Under speed/freq warning
bit11: Over speed failure
bit12: Over speed/freq warning
bit13: Low fuel level failure
bit14: Low fuel level warning
bit15: Battery low and high level
failure
40083
bit0: Battery low and high level
warning
bit1: Not used
bit2: Low coolant level failure
bit3 : Controller is not in auto
bit4: Failure has occurred
bit5 : Cranking rest active
bit6: Controller is in RUN mode (after
crank success)
bit7: Controller is cranking
bit8: Exerciser pre-alarm active (this