User manual

121 of 148
D.3 CT’s (Current Transformers)
Table 31 – Current Transformers Part List
CT Description
Stock Code
Manufacturer’s Part No.
100A:5A
ACC0045
PC&S-546-100-L
200A:5A
ACC0046
PC&S-546-200-L
300A:5A
ACC0047
PC&S-546-300-L
500A:5A
ACC0048
PC&S-546-500-L
600A:5A
ACC0049
PC&S-546-600-L
1000A:5A
ACC0050
PC&S-546-1000-L
1500A:5A
ACC0057
PC&S-546-1500-L
D.4 Senders
Senders are required if display of engine parameters, warnings and failures are
required. Otherwise switches could be used if only failure indication and
shutdown is required.
Table 32 – Senders Part List
Sender Description
Stock Code
Part # Description
STEWART & WARNER – Oil
Pressure*
ACC0108
279B-F 1/8 3/8" NPT
Sensata – Electronic Oil
Pressure**
ACC0122
67CP-0320150GFNA0C
0-5VDC, 0-150 PSI, 1/4"
NPTF-2A
Datcon – Temperature, 1/8”
ACC0027
DATCON 02022-00 1/8”
NPTF-27
Datcon – Temperature, 3/8”
ACC0098
DATCON - 02024-00 3/8"
NPTF-18
Datcon – Temperature, 1/2”
ACC0099
DATCON - 02025-00 1/2"
NPTF-14
* Can use “DATCON 1” on analog input pins 3 or 4. Same as old DATCON oil pressure
sender (ACC0074). ACC0074 is no longer offered for sale.
** Use analog input pin 6. Set Signal Source in Oil Pressure menu to sender3. Note the
GSC400 only reads from 0 to 100PSI. Above 100PSI it the GSC400 continues to read
100PSI.
D.5 GSC400 replaceable 12/24VDC relays
The GSC400 controller is designed to operate in either 12 or 24 VDC battery
start systems. When operating in 12VDC systems the fuel, crank and extra relays
need to be rated 12VDC coil. When operating in 24VDC systems these relays
need to be rated 24VDC coil. To maintain the UL rating, the HASCO relays must
be used.