User manual

118 of 148
Under Voltage Failure
AC Voltage Phase B
Under Voltage
Warning
5s
AC Voltage Phase B
Over Voltage Failure
8s
AC Voltage Phase B
Over Voltage Warning
5s
AC Current Phase B
Over Current Failure
5s
AC Current Phase B
Over Current Warning
4s
EPS Supplying Load
(>5%) Phase B
4.5s
AC Voltage Phase C
Under Voltage Failure
8s
AC Voltage Phase C
Under Voltage
Warning
5s
AC Voltage Phase C
Over Voltage Failure
8s
AC Voltage Phase C
Over Voltage Warning
5s
AC Current Phase C
Over Current Failure
5s
AC Current Phase C
Over Current Warning
4s
EPS Supplying Load
(>5%) Phase C
4.5s
AC Frequency
Under Frequency
Failure
8s
Under Frequency
Warning
5s
Over Frequency
Failure
8s
Over Frequency
Warning
5s
Speed
Under Speed Failure
8s
Under Speed Warning
5s
Over Speed Failure
1s
Over Speed Warning
1.5s
Speed Show False
Cranking
1.75s
Speed show Crank
Success
1s
Speed Show Over
Crank warning
3~60s
User settable.
Decreased to 3s if
locked rotor detected.
Speed Show Over
Crank failure
User settable (crank
tries, crank duration,
rest time) or 3s from
when locked rotor is