User manual
116 of 148
Appendix C GSC400 Fixed Warning/Failure/Event
Delays
The below table lists the fixed delays of the GSC400.
Table 28 – GSC400 Debounce Times
Condition
Time
Notes
Digital Inputs
Low oil pressure
failure
2.0s
Triggers in RUN mode
after 10s bypass
delay.
Low air pressure
failure
3.25s
Triggers only in
modes from Delay to
Start to Crank
Success.
Low hydraulic
pressure failure
3.5s
EPS supplying load
failure
3.75s
EPS supplying load
indication
3.75s
Triggers only in RUN
mode after crank
success.
Low coolant level
failure
3.0s
Can trigger in OFF,
AUTO, and RUN
modes.
Auxiliary failure
1.0s
Auxiliary warning
2.5s
Charger fault 1
warning
3.0s
Charger fault 2
warning
3.0s
High fuel warning
3.0s
User configurable
warning #1
3.0s
User selectable
trigger.
User configurable
warning #2
3.0s
User configurable
failure #1
3.0s
user configurable
failure #2
3.0s
Analog Inputs
High Engine
Temperature Failure
6s
High Engine
Temperature Failure
(switch setting)
4.5s
High Engine
Temperature Warning
5s
Oil Pressure Failure
6s
Oil Pressure Failure
(switch setting)
4.25s