Over Volt Warn 3
500 VAC (480VAC)
Over Volt Fail 3
520 VAC
Under Volt Warn 3
460 VAC
Under Volt Fail 3
440 VAC
Over Volt Warn 4
630 VAC (600VAC)
Over Volt Fail 4
650 VAC
Under Volt Warn 4
570 VAC
Under Volt Fail 4
550 VAC
AC Current
Current source
Enable
Turns Ratio
100A:5A
Over Current Warn 1
90 A
Over Current Fail 1
100 A
Over Current Warn 2
80 A
Over Current Fail 2
90 A
Over Current Warn 3
20 A
Over Current Fail 3
25 A
Over Current Warn 4
15 A
Over Current Fail 4
20 A
Engine Logic
Delay to Start
0 seconds
Pre-heat Time
0 seconds
Crank Time
15 seconds
MidHeat Time
0 seconds
Crank Rest Time
15 seconds
Crank Attempts
3
Fuel Crank Rest
Enable
False Restart
Enable
Post-Heat Time
0 seconds
ETS On Duration
0 seconds
Warm-up Time
600 seconds
Crank Disconnect
650 RPM
Cool Down Delay
0 seconds
Crank Oil pres
0 PSI
Shut Inhib Src
Disabled
Shut Inhib Thr
10.0 PSI
Bypass Cooldwn
Disable
Digital Output Setup
All selections apply
to each individual
output
Extra Relay
Glowplug
Output A
Disable
Output B
Disable
Output C
Disable
Output D
Disable
Output E
Disable
Output F
Disable
Output G
Disable
Output H
Disable
Exerciser setup
Exerciser Enable
Disable
Run Duration
30 minutes
Pre-Alarm Delay
5 minutes
Repeat Frequency
336 hours (14 days)
Start Hour
12
Start Date
8