User manual

113 of 148
Aux Analog 2
Input Pin Disable
Signal Source Switch
Bypass Delay 10s
Switch Setting Closed = Fail
Shorted Sender Disable
Open Sender Disable
Temp Units Fahrenheit
Temp High Warn 250.0F
Temp High Fail 265.0F
Temp Low Warn 75.0F
Temp Low Fail 50.0F
Pres Units PSI
Pres High Warn 95.0 PSI
Pres High Fail 100.0 PSI
Press Low Warn 50.0 PSI
Press Low Fail 10.0 PSI
Level Units Percentage
Level High Warn 90.0%
Level High Fail 95.0%
Level Low Warn 5.0%
Level Low Fail 0.0%
Analog Group Pressure
Speed Sensing
Signal Source
Generator Output
Rated Freq
60 Hz
Rated RPM
1800 RPM
Over Speed Warn
1950 RPM
Over Speed Fail
2050 RPM
Under Speed Warn
1650 RPM
Under Speed Fail
1550 RPM
AC Frequency
Frequency
Disconnect
22 Hz
Over Freq Warn
70 Hz
Over Freq Fail
75 Hz
Under Freq Warn
50 Hz
Under Freq Fail
45 Hz
AC Voltage
Voltage Source
Enable
Voltage Display
Line-Neutral
Voltage Group
Group #1 (Single)
Group 1 Setting
3 Wire Single
Group 3 Setting
Normal Voltage
Group 4 Setting
Three Phase
Over Volt Warn 1
250 VAC (120/240VAC – 3
wire)
Over Volt Fail 1
260 VAC
Under Volt Warn 1
230 VAC
Under Volt Fail 1
220 VAC
Over Volt Warn 2
220 VAC (120/208VAC)
Over Volt Fail 2
230 VAC
Under Volt Warn 2
195 VAC
Under Volt Fail 2
185 VAC