User manual

112 of 148
Oil Level
Input Pin
Disable
Signal Source
Switch
Bypass Delay
10 Seconds
Switch Setting
SW Closed = Fail
Shorted Sender
Disable
Open Sender
Disable
Units
Percentage
Warning Level
10%
Failure Level
5%
Fuel In Basin
Input Pin
Disable
Signal Source
Switch
Bypass Delay
11 Seconds
Switch Setting
SW Closed = Fail
Shorted Sender
Disable
Open Sender
Disable
Units
Percentage
Warning Level
2%
Failure Level
5%
Low Engine
Temperature
Input Pin
Disable
Signal Source
Switch
Bypass Delay
10 Seconds
Switch Setting
SW Closed = Fail
Shorted Sender
Disable
Open Sender
Disable
Units
Fahrenheit
Warning Level
75ºF
Aux Analog 1
Input Pin Disable
Signal Source Switch
Bypass Delay 10s
Switch Setting Closed = Fail
Shorted Sender Disable
Open Sender Disable
Temp Units Fahrenheit
Temp High Warn 250.0F
Temp High Fail 265.0F
Temp Low Warn 75.0F
Temp Low Fail 50.0F
Pres Units PSI
Pres High Warn 95.0 PSI
Pres High Fail 100.0 PSI
Press Low Warn 50.0 PSI
Press Low Fail 10.0 PSI
Level Units Percentage
Level High Warn 90.0%
Level High Fail 95.0%
Level Low Warn 5.0%
Level Low Fail 0.0%
Analog Group Pressure